PUSH-PULL LIQUID RECOVERY OPERATION
1. Connect the unit as shown in Dia-
gram 2.
2. Open both valves on the Recovery
Tank.
3. Open
DISCHARGE valve on CR
unit.
4. Rotate the center valve to the
“SELF-CLEARING”
position.
5. Turn power switch “ON” position.
6. Once unit has started, open the
SUCTION valve on the CR unit to
start the refrigerant flow.
7. Monitor the optional inline sight
glass for liquid refrigerant move-
ment.
8. Once liquid refrigerant is no longer present, close recovery tank vapor valve.
When the SUCTION gauge falls into a vacuum close SUCTION valve and
turn unit OFF.
VAPOR
VALVE
LIQUID
VALVE
LIQUID
SERVICE
PORT
REFRIGERANT
CONTAINING
UNIT TO BE
SERVICED
CR UNIT
SCALE
RECOVERY
TANK
REFRIGERANT
SIGHT GLASS
VAPOR
SERVICE
PORT
DIRECT VAPOR OR LIQUID RECOVERY OPERATION
1. Connect the unit as shown in Dia-
gram 1.
2. Open the vapor valve on the Recov
-
ery Tank.
3. Open
DISCHARGE valve on CR
unit.
4. Rotate the center valve to the
“RE-
COVERY”
position.
5. Turn power switch to “ON” position.
6. Once unit has started, open the
SUCTION valve on the CR unit to
start the refrigerant flow.
NOTE: If liquid refrigerant is present, a hammering sound will come from
the compressor. Use the
SUCTION valve to meter or regulate the incoming
refrigerant until the hammering sound goes away. The
SUCTION gauge
will read the regulated pressure to the compressor.
7. Monitor the suction gauge until it falls below the required vacuum level.
8. Rotate the center valve to the SELF-CLEARING
position. Again monitor
suction gauge. Once the gauge reads a vacuum, Close SUCTION valve,
turn unit OFF.
SCALE
RECOVERY
TANK
REFRIGERANT
CONTAINING
UNIT TO BE
SERVICED
VAPOR
VALVE
CR UNIT
SERVICE
PORT